Roller shutter control with automatic and manual operation

Regular price €17,90 EUR
Regular price Sale price €17,90 EUR
Sale Sold out
Description

The Roller Shutter Control Module (FB) controls a roller shutter either manually via a push button or automatically via sunrise/sunset and brightness sensors. Interlocking mechanisms, a runtime timer, and automatic switching ensure safe and convenient operation. The module is designed for LOGO! 8.3/8.4.

Note: Not for safety purposes. For comfort functions and building technology only.

Electrical installation work may only be carried out by qualified electricians. .

How it works
1) Operating mode switching
  • Automatic switch: Input I3 determines whether manual or automatic operation is active.
  • Manual operation: Buttons I1 (UP) and I2 (DOWN) control the roller shutter directly via timers B006 / B007 (30 s each).
  • Automatic operation: Signals from the sunrise/sunset block and brightness sensor automatically determine the direction of travel.
  • When switching from manual to automatic mode, the manual command is reset to avoid double trips.
2) Astronomical time control
  • LOGO! block B021/B022 calculates sunrise and sunset based on the set location.
  • Exit A: Sunrise → Roller shutter opens (UP).
  • Exit B: Sunset → Roller shutter closes (AB).
  • The signals are only evaluated if I3 = 1 (automatic operation active).
3) Brightness sensor
  • Analog input: AI1 measures 0–10 V (e.g., 0–1000 lux).
  • Scaling: via analog block B017 with Gain = 100 , Offset = 0 .
  • Threshold values: On = 400 Lux (bright), Off = 300 Lux (dark).
  • In darkness, the closing command (CLOSED) is automatically triggered; in light, the opening command (OPEN) is triggered.
4) Roller shutter OPEN
  • I1 → Trigger for Timer B006 (30 s ON time).
  • Automatic signal “sunrise” or “bright” → additional trigger.
  • Interlock: Q1 active ⇒ Q2 locked.
  • Optional: Limit switch I5 for switching off when the end position is up.
5) Roller shutter AB
  • I2 → Trigger for Timer B007 (30 s AB time).
  • Automatic signal “sunset” or “dark” → additional trigger.
  • Interlock: Q2 active ⇒ Q1 locked.
  • Optional: Limit switch I6 for switching off when the end position is down.
6) Security & Priorities
  • Priority: Manual commands > Automatic > Safety functions.
  • Wind/rain alarm: Input I4 forces "OPEN" and blocks "OFF".
  • Both directions of travel are electrically locked (no synchronization).
Technical details
  • Inputs: I1 (AUF) , I2 (AB) , I3 (Automatik EIN/AUS) , I4 (Sicherheit) , AI1 (Helligkeit)
  • Outputs: Q1 (AUF) , Q2 (AB)
  • Timer: B006 , B007 (30 s runtime)
  • Automatic: B021/B022 (Astronomical time control)
  • Analog block: B017 (scaling/thresholds)
  • LOGO! version: 8.3 / 8.4
  • Programming language: FUP
Diagnosis & Status
  • Manual operation active (I3 = 0)
  • Automatic mode active (I3 = 1)
  • ON active (Q1 = 1)
  • AB active (Q2 = 1)
  • Sensor dark (AI1 < 300 Lux)
  • Sensor bright (AI1 > 400 Lux)
  • Safety interlock active (Q1 ≠ Q2)
Applications
  • Individual roller shutter or blind control in the residential building
  • Group control (multiple windows via central button)
  • Light/heat control in workshop or office
  • Automatic shading with brightness sensor
compatibility
  • Siemens LOGO! Soft Comfort 8.3 / 8.4
  • Simulation via LOGO! Soft Comfort / PLCSIM
  • Optional LOGO! web server interface for status and manual control
Support
  • Adjusting travel time, brightness thresholds, or location data
  • Expansion to include wind/rain sensor or group control
  • Integration into LOGO! web servers or Modbus systems
  • Creation as a finished .lsc file for LOGO! Soft Comfort